EA400

The EnviroAlert ® EA400 critical-environment monitoring device provides visibility of up to 4 environmental factors including temperature, humidity and water detection. When a condition deviates from the predetermined threshold both visual and audible (Piezo buzzer required – 3rd party buzzer add on) notifications occur. When integrated into a security panel, the system allows for the real-time notification of an incident and immediate corrective action.

For Information on NIST Calibrated Sensors: Click Here

Features
  • Simultaneous operation of four sensors
  • Easy to read LCD display
  • 8 event incident memory, including time and date
  • Auxiliary output relay for local audible alarm
  • Auxiliary alarm silence feature with 10 minute timer
  • Offset sensor calibration adjustment
  • Tamper proof lock setting
  • Alarm notification via dry contact relay to any alarm panel
Sensors

Other Accessories

Q: How do I unlock the EA400 for programming?

A: Simultaneously press and release the ALARM SILENCE and ENTER keys.  The (Unlocked) icon appears.  Sometimes you will need to do this more than once.  You may need to have the customer check the buttons to make sure one is not stuck down or sometimes if you power cycle the unit that will help. 

Q: Does the unit store the settings if the unit loses power?

A: It will maintain the programming on the zones, but you will have to reset the time and date. 

Q: How do I turn off a zone?

A: The unit has to be unlocked.  Push the zone button, use the arrow up or arrow down to go to the zone you would like to turn off, once you are on the correct zone, push enter.  The next setting needs to be changed to NO (Not operational) and then push enter.  This will turn off the zone. 

Q: Can you use multiple temperature probes on an input?

A: No, you can only use one temperature probe per input. 

Q: Is there a way to send a separate high and a separate low to my alarm panel?

A: This can be done on an EA400 by using an input (zone) for a high limit and another input (Zone) for a low limit.  On the EA200 you would need to use the onboard sensor (zone 1) for one of the limits and then use a probe on input 2 (zone) and program accordingly.  NOTE: In this instance, you would need to select an input (zone) for the high limit and program that to your high and you would program the low limit on that input (zone) to an extreme low so you would not get the notification on the low side.  You would do the opposite for the next input (zone) you would set the high limit to the extreme and set the low limit to what you actually wanted. 

Common EA400 Errors